General Information

Size Range: 1/2” through 36”
Material: Carbon Steel acc. to the MSS SP 58-TABLE A2/A2M
Service: Designed for suspension of insulated or non-insulated stationary pipes.
Installation: Vertical adjustments are possible once the pipe is in place. The lower nut is used to adjust the pipeline to the required elevation. The top nut is used to prevent loosening due to the vibration. The top nut should be tightened after adjustment. The top nut must securely be tightened to assure proper performance of hanger after adjustment.
Ordering: Specify pipe size, figure number, name and finish.
Finish:

  • Electro-Galvanization acc. to ASTM B 633/ASTM F 1941
  • Hot Dipped Galvanized. (HDG) acc.to ASTM A 153/123

Approvals:

  • Complies with Manufacturer’s Standardization Society MSS SP-58 & MSS SP-69 – Type 1
  • Complies with NFPA-13 Standard for the Installation of Sprinkler Systems.

Certification: FM Approval and UL listed

Technical Specifications

 

Code No Code No for HDG Size Max. Selected Size of Steel A B C D E F Max Recom. Load kN Weight per 100 pcs. (lbs) Cert.
Inch DN OD OD Inch Upper Lower Inch Inch Inch Inch
IEKCHL015 IEKCHL015H ½” (15) 21,3 31/32 3×25 3×25 M10 M6 2 19/32 1 31/32 1 3/8 13/32 2,7 31 UL
IEKCHL020 IEKCHL020H ¾” (20) 26,9 1 7/32 3×25 3×25 M10 M6 3 2 1/4 1 21/32 15/32 2,7 35 FM/UL
IEKCHL025 IEKCHL025H 1” (25) 33,7 1 1/2 3×25 3×25 M10 M6 3 11/32 2 15/32 1 27/32 19/32 2,7 40 FM/UL
IEKCHL032 IEKCHL032H 1 ¼” (32) 42,4 1 13/16 3×25 3×25 M10 M6 3 29/32 2 27/32 2 1/4 13/16 2,7 44 FM/UL
IEKCHL040 IEKCHL040H 1 ½” (40) 48,3 2 1/16 3×25 3×25 M10 M8 4 9/32 3 1/8 2 13/32 29/32 2,7 53 FM/UL
IEKCHL050 IEKCHL050H 2” (50) 60,3 2 17/32 3×25 3×25 M10 M8 5 11/32 3 31/32 3 7/32 1 1/2 2,7 62 FM/UL
IEKCHL065 IEKCHL065H 2 ½” (65) 76,1 3 5/32 5×30 5×30 M12 M10 6 3/8 4 19/32 3 21/32 1 5/8 5,0 146 FM/UL
IEKCHL080 IEKCHL080H 3” (80) 88,9 3 21/32 5×30 5×30 M12 M10 6 25/32 4 23/32 3 25/32 1 1/2 5,0 157 FM/UL
IEKCHL090 IEKCHL090H 3 ½” (90) 101,6 4 3/16 5×30 5×30 M12 M10 7 3/8 5 1/16 4 1/8 1 1/2 5,0 170 FM/UL
IEKCHL100 IEKCHL100H 4” (100) 114,3 4 11/16 6×30 5×30 M16 M10 8 1/16 5 1/2 4 17/32 1 11/16 6,3 198 FM/UL
IEKCHL112 IEKCHL112H 5 1/32 6×30 5×30 M16 M10 8 21/32 5 29/32 4 3/8 1 15/32 6,3 207
IEKCHL125 IEKCHL125H 5” (125) 139,7 5 9/16 6×30 5×30 M16 M12 9 1/8 6 1/8 4 19/32 1 21/32 6,3 238 FM/UL
IEKCHL134 IEKCHL134H 6 1/16 6×30 5×30 M16 M12 10 3/32 6 13/16 5 9/32 1 21/32 6,3 254
IEKCHL150 IEKCHL150H 6” (150) 168,3 6 11/16 6×40 5×40 M20 M12 10 13/32 6 27/32 5 1/16 1 15/32 8,6 344 FM/UL
IEKCHL185 IEKCHL185H 7 7/8 6×50 5×50 M20 M16 11 7/8 7 23/32 5 15/16 1 9/16 8,6 560
IEKCHL200 IEKCHL200H 8” (200) 219,1 8 21/32 6×50 5×50 M20 M16 12 29/32 8 5/16 6 17/32 1 11/16 8,9 593 UL
IEKCHL224 IEKCHL224H 9 29/32 10×50 6×50 M20 M20 14 13/16 9 9/16 7 5/8 1 15/16 16,0 957
IEKCHL250 IEKCHL250H 10” (250) 273,0 10 25/32 10×50 6×50 M20 M20 15 3/4 10 3/32 8 5/32 1 15/16 16,0 1021 UL
IEKCHL280 IEKCHL280H 11 9/16 10×50 6×50 M20 M20 16 25/32 10 23/32 8 5/32 1 15/16 16,0 1085
IEKCHL285 IEKCHL285H 12 1/8 10×50 6×50 M20 M20 17 3/8 11 1/32 9 3/32 2 9/32 16,0 1118
IEKCHL295 IEKCHL295H 12 3/8 10×50 6×50 M20 M20 17 23/32 11 1/4 9 11/32 2 9/32 16,0 1133
IEKCHL298 IEKCHL298H 12 27/32 10×50 6×50 M20 M20 457,0 11 5/16 9 3/8 2 9/32 16,0 1283